Overhead Service Attachment
 Notes:
- LEC will furnish the meter, service drop conductor and service
attachment to the conduit mast. The Cooperative will connect
the member’s conductors to the Cooperative’s service
drop.
- The consumer will furnish the service entrance
conduit, conductor and meterbase in accordance to code
requirements. A minimum of 18” member conductor must
extend from the weatherhead.
- A strong enough service mast must be mounted
on the side nearest LEC’s distribution pole. A clear
path must exist between service drop attachment and pole.
Avoid service wire
overhang above roof, or provide code clearance.
- Energizing
of Consumers service is contingent upon a State
or City electrical inspection.
- See Exhibits A & B for details of clearance
requirements.
Temporary Overhead Installation
 Notes:
- Temporary pole should be located as specified by the
Cooperative.
- Consumer shall supply temporary pole, meterbase,
main disconnect, and grounds to N.E.C. construction code
specifications.
- The
Cooperative will provide maximum 30’ service drop
and install meter.
- Energizing of consumer’s service
is contingent upon an approved State or City electrical
inspection.
Overhead Service With Underground Feeder

Notes:
- All electric connections, equipment, and equipment grounds
shall comply with the National Electric Safety Code.
- The consumer
shall furnish and maintain all conduit, conduit straps,
grounds, disconnects, meterbase, and all conductors
beyond LEC’s point of delivery.
- LEC shall furnish and
maintain the meter, service drop, pole, guy wire, and anchor.
- Energizing
of consumers service is contingent upon an approved
State or City electrical inspection.
Overhead Service With Overhead Feeder

Notes:
All electric connections, equipment, and equipment grounds
shall comply with the National Electric Safety Codes.
The consumer
shall furnish and maintain all conduit, conduit straps, grounds,
disconnects, meterbase, and all conductors
beyond LEC’s point of delivery.
LEC shall furnish and
maintain the meter, service drop, pole, guy wire, and anchor.
Energizing
of consumer’s service is contingent upon an
approved State or City electrical inspection.
|