Underground Services
Lane Electric Cooperative will need to inspect all ditches and conduit prior to backfilling. Lane Electric will provide and install a service conductor. Please remember to call Utility Notification Center 1-800-332-2344 48 hours prior to digging.
Temporary Underground Installation

Notes:
- Consumer will supply conductors long enough to be connected inside LEC’s transformer or secondary box. A maximum of 3 feet from pole to transformer or secondary box.
- Consumer will supply all trench, meterbase, grounds, pole, and disconnect switch.
- LEC will connect the consumer’s wire to the transformer or secondary box and install the meter.
- Energizing of consumer’s service is contingent upon an approved State or City electrical inspection.
Underground Service With An Underground Feeder

Notes:
- All electrical connections, equipment and equipment grounds shall comply with the National Electrical Safety Codes.
- The Consumer shall furnish and maintain a 6”x6”x10’ pressure treated wood post, all conduit, conduit straps, grounds, meterbase, disconnects, and electrical cable beyond the meter, and shall open and backfill a service trench 36” minimum depth from the L.E.C. equipment to the desired meterbase location.
- The Cooperative shall furnish and maintain the meter and electrical cable from the transformer to the meter.
- Before the cooperative energizes the meterbase, the base must be inspected and approved by the State or City Electrical Inspectors and the cooperative personnel. The service trench must be completely backfilled.
- Before you dig, call 48 hours in advance to the Utility Notification Center 1-800-332-2344.
Underground Service To A Building

Notes:
- All electrical connections, equipment and equipment grounds shall comply with the National Electrical Code.
- The consumer shall furnish and maintain all conduit, conduit straps, grounds, meterbase, disconnects, and electrical cable beyond the meter, and shall open and backfill a service trench 36” minimum depth from the LEC equipment to the desired meterbase location.
- The Cooperative shall furnish and maintain the meter, electrical cable from LEC equipment to the meter.
- Before the cooperative energizes the meterbase, the base must be inspected and approved by the State or City Electrical Inspectors and the cooperative personnel. The service trench must be completely backfilled after approved inspection.
- Before you dig, call 48 hours in advance to the Utility Notification Center 1-800-332-2344.